Attackers Remotely Defrosted Refrigerators at Hundreds of French Supermarkets, and the Exposed Danfoss Controllers Were Searchable Online

Obiguard Research Team·October 13, 2026·4 min read

Overnight on Sunday 11 October, attackers remotely switched refrigeration units at French supermarkets into defrost mode, warming stock across potentially hundreds of stores. According to BleepingComputer, the attack reportedly targeted Danfoss refrigeration controllers running older control software, and French outlets put the number of affected stores between 250 and 350. No confirmed store count has been published and no threat actor has been named.

What is known

  • Chains named: Intermarché, Coopérative U, Carrefour Market, Monoprix, Leclerc and Super U. Intermarché's statement also mentioned Netto.
  • Method: the attackers abused the controllers' built-in automatic defrost function to raise temperatures, rather than destroying equipment.
  • Impact: food waste and financial losses. Intermarché said products were being removed from affected units and described a cyberattack "reportedly affecting a service provider that manages refrigeration systems."
  • Official response: Coopérative U's president called the attack "unprecedented" and "unacceptable." EU agriculture commissioner Christophe Hansen condemned it, and the Paris prosecutor's office has opened an investigation, per AFP.

Danfoss, Leclerc and Coopérative U had not responded to BleepingComputer's requests for comment at the time of reporting.

What has not been confirmed

The reporting does not say how the controllers were compromised. Danfoss AK-SM 8xxA series devices are used to manage refrigeration and HVAC in food retail, and two flaws in that product line were already public:

CVE Type Earlier warning
CVE-2025-41450 Authentication bypass CISA bulletin SB25-132, May 2025
CVE-2025-41451 Command injection CISA bulletin SB25-237, August 2025

Claroty's Team82 found both and, in August, published research showing how they could be chained for remote code execution on internet-reachable AK-SM 800A management interfaces. Treat the link to this week's attack as plausible but unconfirmed: nothing published so far says these CVEs were the entry point.

How exposed these devices are

Predicta Lab CEO Baptiste Robert counted 2,752 exposed Danfoss systems on Monday, 1,590 of them in France, and Shodan tracks more than 4,500 Danfoss devices reachable from the internet. That is the practical lesson: a controller that answers on a public address is findable by anyone with a search engine, whether or not a specific bug is involved.

A separate incident was announced the same day: Ahold Delhaize said it took some systems offline after a "cybersecurity incident." There is no evidence so far that the two are connected.

What operators should check

The reporting offers no vendor remediation guidance, so these are general steps rather than a Danfoss-specific fix:

  1. Find your own exposure. Search Shodan or Censys for your public IP ranges and any managed-service provider ranges that run refrigeration or building controllers on your behalf.
  2. Remove direct internet access to management interfaces. Put them behind a VPN or an allow-listed jump host.
  3. Apply vendor firmware for the CVEs above and confirm the version with your service provider, not just your own records.
  4. Ask your providers which of your stores' devices they manage and how those are reached.
  5. Set temperature alarms that do not depend on the controller. An independent sensor that pages a person catches a defrost cycle before the stock is lost.

Where Obiguard SOC fits

This incident is a monitoring problem as much as a patching problem. The devices were reachable, the change that mattered was a legitimate-looking configuration action, and the first sign to the victim was warm product. Obiguard SOC is built to bring remote-access logs, VPN and firewall events, and alerts from operational and building systems into one place, so that an unfamiliar source address issuing a defrost command to a store controller at 2 a.m. is something an analyst sees, not something discovered in the morning.

It will not patch a controller or hide it from Shodan, and it cannot alert on a log source nobody forwarded. What it does is shorten the time between a bad action and a person noticing, and keep the evidence together for the investigation that follows.

The question to take away

If someone told your refrigeration or building controllers to change state tonight, which system would log it, and who would be looking?